July/August/September 2021 I 57 Table 3 references M-ratings for UL system listings using traditional sealant technology. These type products generally do not have as high of a movement rating because they adhere to the penetrating item and cure to a more hardened state. Comparing results, systems with preformed tech- nology, which includes pathway devices for data cables, offer significantly more movement capability. TABLE 3: M-ratings for traditional sealant technology. Table includes reference information for comparison only. See listings for full system details and requirements. Source: UL.com. Listing F Rating Product Penetrant Movement Y Direction Z Direction WL 1054 1 hr FS-One Max 2" Steel Pipe/ Conduit 5% 0.25" WL 1290 1 hr CP 606 2" Steel Pipe 5% 0.25" WL 2244 1 hr (with movement) FS-One Max 2" PVC Pipe 5% 0.25" In many cases, this is as much as 100 percent versus only 5 percent for sealant systems. Acoustics Acoustics has become a trending topic in building design and construction. Numerous sources of airborne and structural-borne sound exist, impacting most any building structure including data centers (Figure 7). Aircraft noise Traffic noise House installations Household appliances Domestic noise Workplace noise Airborne sound Structure-borne sound FIGURE 7: Illustration of the various and many airborne and structure-borne sounds.