jumper cable permanently connected to the piping on either side of the coupling as described in NFPA 77. The cable should be securely attached to either a flange bolt or a lug that's welded to the pipe. Avoid attaching the jumper cable using clamp-style connectors, which can loosen or have inadequate metal contact over time. The jumper cable should be 10-AWG stranded wire or larger and should be long enough to connect across the coupling but not long enough to create a trip or snag hazard. An uninsulated grounding strap or cable wrapped around the coupling and pipe sections and held in place by springs is inadequate. Dirt and buildup on the pipe and cable can insulate the cable from the pipe and result in poor continuity. Plastic or rubber hoses used to pneumatically convey bulk solids or for dust removal should contain conductive helical internal wiring, which should be attached to the pipe connections at both ends of the hose. The internal wiring reinforces the hose and provides electrical continuity along the conveying pathway. Periodically check pneumatic conveying and dust collection piping and ductwork for proper grounding and to ensure that there's very little or no electrical resistance across joints and couplings. Filling a large bin or silo with a bulk solid material can cause static electric or brush discharges, which may have enough energy to ignite the dust in the headspace above the material pile even if the silo is grounded. These discharges may create crackling noises and flashes during filling (per NFPA 77, Section 5.3.8). If this is a concern for your operation, contact your corporate safety manager. 81 PBE January 2016 Figure 1 External clamp coupling Courtesy of Morris Coupling Company Flange Rubber gasket Grounding strap